Constants
The module keba_keenergy_api.constants defines the endpoints and their values, e.g. for read_data() and write_data(). Paths are relative to PAYLOAD_PREFIX (APPL.CtrlAppl), %s is replaced by the zero-based device index.
Endpoints
System
The system endpoint settings.
| Member | Type | Writable | Values | Path |
|---|---|---|---|---|
BUFFER_TANK_NUMBERS | int | no | sParam.options.systemNumberOfBuffers | |
HOT_WATER_TANK_NUMBERS | int | no | sParam.options.systemNumberOfHotWaterTanks | |
HEAT_PUMP_NUMBERS | int | no | sParam.options.systemNumberOfHeatPumps | |
HEAT_CIRCUIT_NUMBERS | int | no | sParam.options.systemNumberOfHeatingCircuits | |
SOLAR_CIRCUIT_NUMBERS | int | no | sParam.options.systemNumberOfSolarCircuits | |
EXTERNAL_HEAT_SOURCE_NUMBERS | int | no | sParam.options.systemNumberOfExtHeatSources | |
SWITCH_VALVE_NUMBERS | int | no | sParam.options.systemNumberOfSwitchValves | |
HAS_PHOTOVOLTAICS | str | no | BoolEnum | sParam.options.hasPhotovoltaics |
HAS_OUTDOOR_TEMPERATURE | str | no | BoolEnum | sParam.options.hasOutdoorTemp |
OPERATING_MODE | int | yes | SystemOperatingMode | sParam.param.operatingMode |
OUTDOOR_TEMPERATURE | float | no | sParam.outdoorTemp.values.actValue | |
CPU_USAGE | float | no | sProcData.globalCpuTimePercent | |
WEBVIEW_CPU_USAGE | float | no | sProcData.processStatus[0].cpuTimePercent | |
WEBSERVER_CPU_USAGE | float | no | sProcData.processStatus[1].cpuTimePercent | |
CONTROL_CPU_USAGE | float | no | sProcData.processStatus[2].cpuTimePercent | |
RAM_USAGE | int | no | sProcData.RAMstatus.tmpfs | |
FREE_RAM | int | no | sProcData.totFreeRAM |
BufferTank
The buffer tank endpoint settings.
| Member | Type | Writable | Values | Path |
|---|---|---|---|---|
NAME | str | yes | sParam.bufferTank[%s].param.name | |
CURRENT_TOP_TEMPERATURE | float | no | sParam.bufferTank[%s].topTemp.values.actValue | |
CURRENT_BOTTOM_TEMPERATURE | float | no | sParam.bufferTank[%s].midTemp.values.actValue | |
OPERATING_MODE | int | yes | BufferTankOperatingMode | sParam.bufferTank[%s].param.operatingMode |
STANDBY_TEMPERATURE | float | yes | sParam.bufferTank[%s].param.backupTemp | |
TARGET_TEMPERATURE | float | no | sParam.bufferTank[%s].values.setTemp | |
EXCESS_ENERGY_TARGET_TEMPERATURE | float | yes | sParam.bufferTank[%s].param.excessEnergyTemp.value | |
EXCESS_ENERGY_TARGET_TEMPERATURE_HYSTERESIS | float | yes | sParam.bufferTank[%s].param.excessEnergyTemp.hyst | |
OUTDOOR_TEMPERATURE_EXCESS_ENERGY_LIMIT | float | yes | sParam.bufferTank[%s].param.thresholdOutTempExcessEnergy.value | |
USE_EXCESS_ENERGY | str | yes | BoolEnum | sParam.bufferTank[%s].param.useExcessEnergy |
EXCESS_ENERGY_MODE | int | no | BufferTankExcessEnergyMode | sParam.bufferTank[%s].values.useExcessEnergy |
HEAT_REQUEST | str | no | BoolEnum | sParam.bufferTank[%s].values.heatRequestTop |
COOL_REQUEST | str | no | BoolEnum | sParam.bufferTank[%s].values.coolRequestBot |
HotWaterTank
The hot water tank endpoint settings.
| Member | Type | Writable | Values | Path |
|---|---|---|---|---|
NAME | str | yes | sParam.hotWaterTank[%s].param.name | |
CURRENT_TEMPERATURE | float | no | sParam.hotWaterTank[%s].topTemp.values.actValue | |
OPERATING_MODE | int | yes | HotWaterTankOperatingMode | sParam.hotWaterTank[%s].param.operatingMode |
STANDBY_TEMPERATURE | float | yes | sParam.hotWaterTank[%s].param.reducedSetTempMax.value | |
TARGET_TEMPERATURE | float | yes | sParam.hotWaterTank[%s].param.normalSetTempMax.value | |
EXCESS_ENERGY_TARGET_TEMPERATURE | float | yes | sParam.hotWaterTank[%s].param.excessEnergyTemp.value | |
EXCESS_ENERGY_TARGET_TEMPERATURE_HYSTERESIS | float | yes | sParam.hotWaterTank[%s].param.excessEnergyTemp.hyst | |
USE_EXCESS_ENERGY | str | yes | BoolEnum | sParam.hotWaterTank[%s].param.useExcessEnergy |
EXCESS_ENERGY_MODE | int | no | HotWaterTankExcessEnergyMode | sParam.hotWaterTank[%s].values.useExcessEnergy |
HEAT_REQUEST | str | no | BoolEnum | sParam.hotWaterTank[%s].values.heatRequestTop |
HAS_FRESH_WATER_MODULE | str | no | BoolEnum | sParam.options.hotWaterTank[%s].hasFreshWaterModule |
FRESH_WATER_FLOW | str | no | BoolEnum | sParam.hotWaterTank[%s].FreshWater.freshWaterFlow.values.actValue |
FRESH_WATER_MODULE_TEMPERATURE | float | no | sParam.hotWaterTank[%s].FreshWater.freshWaterTemp.values.actValue | |
FRESH_WATER_MODULE_PUMP_SPEED | float | no | sParam.hotWaterTank[%s].FreshWater.freshWaterPump.values.setValueScaled | |
CIRCULATION_RETURN_TEMPERATURE | float | no | sParam.hotWaterTank[%s].circTemp.values.actValue | |
CIRCULATION_PUMP_STATE | str | no | BoolEnum | sParam.hotWaterTank[%s].circPump.pump.values.setValueB |
HeatPump
The heat pump endpoint settings.
| Member | Type | Writable | Values | Path |
|---|---|---|---|---|
NAME | str | yes | sParam.heatpump[%s].param.name | |
STATE | int | no | HeatPumpState | sParam.heatpump[%s].values.heatpumpState |
SUBSTATE | int | no | HeatPumpSubState | sParam.heatpump[%s].values.heatpumpSubState |
OPERATING_MODE | int | yes | HeatPumpOperatingMode | sParam.heatpump[%s].param.operatingMode |
COMPRESSOR_USE_NIGHT_SPEED | str | yes | BoolEnum | sParam.heatpump[%s].HeatPumpPowerCtrl.param.useDayNightSpeed |
COMPRESSOR_NIGHT_SPEED | float | yes | sParam.heatpump[%s].HeatPumpPowerCtrl.param.maxPowerScaledNight | |
CIRCULATION_PUMP_SPEED | float | no | sParam.heatpump[%s].CircPump.values.setValueScaled | |
SOURCE_PUMP_SPEED | float | no | sParam.heatpump[%s].Source.values.setValueScaled | |
FLOW_TEMPERATURE | float | no | sParam.heatpump[%s].TempHeatFlow.values.actValue | |
RETURN_FLOW_TEMPERATURE | float | no | sParam.heatpump[%s].TempHeatReflux.values.actValue | |
SOURCE_INPUT_TEMPERATURE | float | no | sParam.heatpump[%s].TempSourceIn.values.actValue | |
SOURCE_OUTPUT_TEMPERATURE | float | no | sParam.heatpump[%s].TempSourceOut.values.actValue | |
COMPRESSOR_INPUT_TEMPERATURE | float | no | sParam.heatpump[%s].TempCompressorIn.values.actValue | |
COMPRESSOR_OUTPUT_TEMPERATURE | float | no | sParam.heatpump[%s].TempCompressorOut.values.actValue | |
COMPRESSOR | float | no | sParam.heatpump[%s].Compressor.values.setValueScaled | |
CONDENSER_TEMPERATURE | float | no | sParam.heatpump[%s].OverHeatCtrl.values.tempCond | |
VAPORIZER_TEMPERATURE | float | no | sParam.heatpump[%s].OverHeatCtrl.values.tempVap | |
TARGET_OVERHEATING | float | no | sParam.heatpump[%s].OverHeatCtrl.values.setOH | |
CURRENT_OVERHEATING | float | no | sParam.heatpump[%s].OverHeatCtrl.values.actOH | |
EXPANSION_VALVE_POSITION | int | no | sParam.heatpump[%s].OverHeatCtrl.values.stepperPos | |
HIGH_PRESSURE | float | no | sParam.heatpump[%s].HighPressure.values.actValue | |
LOW_PRESSURE | float | no | sParam.heatpump[%s].LowPressure.values.actValue | |
HEAT_REQUEST | str | no | BoolEnum | sParam.heatpump[%s].values.request |
CONSUMING_EXCESS_ENERGY | str | no | BoolEnum | sParam.heatpump[%s].values.consumingExcessEnergy |
EXCESS_ENERGY_OPERATING_TIME | int | no | sParam.heatpump[%s].operationalDataExcessEnergy.operationalTimeS | |
EXCESS_ENERGY_MAX_RUNTIME | int | no | sParam.heatpump[%s].operationalDataExcessEnergy.maxRunTimeS | |
EXCESS_ENERGY_ACTIVATION_COUNTER | int | no | sParam.heatpump[%s].operationalDataExcessEnergy.activationCounter | |
HEATING_POWER | float | no | sParam.heatpump[%s].HeatMeter.values.power | |
HEATING_MASS_FLOW_RATE | float | no | sParam.heatpump[%s].HeatMeter.values.massFlow | |
COOLING_MASS_FLOW_RATE | float | no | sParam.heatpump[%s].CoolMeter.values.massFlow | |
HOT_WATER_POWER | float | no | sParam.heatpump[%s].HotWaterMeter.values.power | |
HOT_WATER_MASS_FLOW_RATE | float | no | sParam.heatpump[%s].HotWaterMeter.values.massFlow | |
COMPRESSOR_POWER | float | no | sParam.heatpump[%s].ElectricEnergyMeter.values.power | |
COP | float | no | sParam.heatpump[%s].values.COP | |
HEATING_ENERGY | float | no | sStatisticalData.heatpump[%s].consumption.heating.energy | |
HEATING_ENERGY_CONSUMPTION | float | no | sStatisticalData.heatpump[%s].consumption.heating.electricalenergy | |
HEATING_SPF | float | no | sStatisticalData.heatpump[%s].EnergyEfficiencyRatioHeat | |
COOLING_ENERGY | float | no | sStatisticalData.heatpump[%s].consumption.cooling.energy | |
COOLING_ENERGY_CONSUMPTION | float | no | sStatisticalData.heatpump[%s].consumption.cooling.electricalenergy | |
COOLING_SPF | float | no | sStatisticalData.heatpump[%s].EnergyEfficiencyRatioCool | |
HOT_WATER_ENERGY | float | no | sStatisticalData.heatpump[%s].consumption.domHotWater.energy | |
HOT_WATER_ENERGY_CONSUMPTION | float | no | sStatisticalData.heatpump[%s].consumption.domHotWater.electricalenergy | |
HOT_WATER_SPF | float | no | sStatisticalData.heatpump[%s].EnergyEfficiencyRatioDomHotWater | |
TOTAL_THERMAL_ENERGY | float | no | sStatisticalData.heatpump[%s].consumption.energy | |
TOTAL_ENERGY_CONSUMPTION | float | no | sStatisticalData.heatpump[%s].consumption.electricalenergy | |
EXCESS_ENERGY_CONSUMPTION | float | no | sStatisticalData.heatpump[%s].consumption.consumedExcessEnergy | |
HEATING_EXCESS_ENERGY_CONSUMPTION | float | no | sStatisticalData.heatpump[%s].consumption.heating.consumedExcessEnergy | |
COOLING_EXCESS_ENERGY_CONSUMPTION | float | no | sStatisticalData.heatpump[%s].consumption.cooling.consumedExcessEnergy | |
HOT_WATER_EXCESS_ENERGY_CONSUMPTION | float | no | sStatisticalData.heatpump[%s].consumption.domHotWater.consumedExcessEnergy | |
TOTAL_SPF | float | no | sStatisticalData.heatpump[%s].EnergyEfficiencyRatio | |
HAS_ACTIVE_COOLING | str | no | BoolEnum | sParam.options.heatpump[%s].hasActiveCooling |
HAS_PASSIVE_COOLING | str | no | BoolEnum | sParam.options.heatpump[%s].hasPassiveCooling |
OPERATING_TIME | int | no | sParam.heatpump[%s].operationalData.operationalTimeS | |
MAX_RUNTIME | int | no | sParam.heatpump[%s].operationalData.maxRunTimeS | |
ACTIVATION_COUNTER | int | no | sParam.heatpump[%s].operationalData.activationCounter | |
HAS_COMPRESSOR_FAILURE | str | no | BoolEnum | sParam.heatpump[%s].FailureCompressor.values.actValue |
HAS_SOURCE_FAILURE | str | no | BoolEnum | sParam.heatpump[%s].FailureSource.values.actValue |
HAS_SOURCE_ACTUATOR_FAILURE | str | no | BoolEnum | sParam.heatpump[%s].FailureActuatorSource.values.actValue |
HAS_THREE_PHASE_FAILURE | str | no | BoolEnum | sParam.heatpump[%s].FailureThreePhase.values.actValue |
HAS_SOURCE_PRESSURE_FAILURE | str | no | BoolEnum | sParam.heatpump[%s].FailureSrcPressure.values.actValue |
HAS_VFD_FAILURE | str | no | BoolEnum | sParam.heatpump[%s].FailureVFD.values.actValue |
ELECTRIC_ENERGY_METER_TYPE | int | no | sParam.options.heatpump[%s].ElectricEnergyMeter.type | |
HEAT_METER_TYPE | int | no | sParam.options.heatpump[%s].HeatMeter.type | |
COOL_METER_TYPE | int | no | sParam.options.heatpump[%s].CoolMeter.type | |
HOT_WATER_METER_TYPE | int | no | sParam.options.heatpump[%s].HotWaterMeter.type |
HeatCircuit
The heat circuit endpoint settings.
| Member | Type | Writable | Values | Path |
|---|---|---|---|---|
NAME | str | yes | sParam.heatCircuit[%s].param.name | |
MODE | int | no | HeatCircuitMode | sParam.options.heatCircuit[%s].type |
HAS_ROOM_TEMPERATURE | str | no | BoolEnum | sParam.options.heatCircuit[%s].hasRoomTemp |
ROOM_TEMPERATURE | float | no | sParam.heatCircuit[%s].tempRoom.values.actValue | |
HAS_ROOM_HUMIDITY | str | no | BoolEnum | sParam.options.heatCircuit[%s].hasRoomHumidity |
ROOM_HUMIDITY | float | no | sParam.heatCircuit[%s].humidityRoom.values.actValue | |
DEW_POINT | float | no | sParam.heatCircuit[%s].dewPoint.values.actValue | |
FLOW_TEMPERATURE_SETPOINT | float | no | sParam.heatCircuit[%s].values.flowSetTemp | |
HAS_MIXER | str | no | BoolEnum | sParam.options.heatCircuit[%s].hasMixer |
MIXER_FLOW_TEMPERATURE | float | no | sParam.heatCircuit[%s].heatCircuitMixer.flowTemp.values.actValue | |
MIXER_RETURN_FLOW_TEMPERATURE | float | no | sParam.heatCircuit[%s].heatCircuitMixer.refluxTemp.values.actValue | |
MIXER_POSITION | float | no | MixerSwitchValvePosition | sParam.heatCircuit[%s].heatCircuitMixer.mixer.values.setValueScaled |
PUMP_STATE | str | no | BoolEnum | sParam.heatCircuit[%s].pump.values.setValueB |
HAS_RETURN_FLOW_TEMPERATURE | str | no | BoolEnum | sParam.options.heatCircuit[%s].hasRefluxTemp |
RETURN_FLOW_TEMPERATURE | float | no | sParam.heatCircuit[%s].tempReflux.values.actValue | |
TARGET_TEMPERATURE | float | no | sParam.heatCircuit[%s].values.setValue | |
USE_EXCESS_ENERGY | str | yes | BoolEnum | sParam.heatCircuit[%s].param.excessEnergy.useExcessEnergy |
EXCESS_ENERGY_MODE | int | no | HeatCircuitExcessEnergyMode | sParam.heatCircuit[%s].values.useExcessEnergy |
EXCESS_ENERGY_TARGET_TEMPERATURE | float | yes | sParam.heatCircuit[%s].param.excessEnergyTemp.value | |
EXCESS_ENERGY_TARGET_TEMPERATURE_HYSTERESIS | float | yes | sParam.heatCircuit[%s].param.excessEnergyTemp.hyst | |
EXCESS_ENERGY_TARGET_COOLING_TEMPERATURE | float | yes | sParam.heatCircuit[%s].param.excessEnergyTempCool.value | |
EXCESS_ENERGY_TARGET_COOLING_TEMPERATURE_HYSTERESIS | float | yes | sParam.heatCircuit[%s].param.excessEnergyTempCool.hyst | |
SELECTED_TARGET_TEMPERATURE | float | no | sParam.heatCircuit[%s].values.selectedSetTemp | |
TARGET_TEMPERATURE_DAY | float | yes | sParam.heatCircuit[%s].param.normalSetTemp | |
TARGET_COOLING_TEMPERATURE_DAY | float | yes | sParam.heatCircuit[%s].param.normalCoolSetTemp | |
HEATING_LIMIT_DAY | float | yes | sParam.heatCircuit[%s].param.thresholdDayTemp.value | |
COOLING_LIMIT_DAY | float | yes | sParam.heatCircuit[%s].param.thresholdDayCoolTemp.value | |
EXCESS_ENERGY_HEATING_LIMIT_DAY | float | yes | sParam.heatCircuit[%s].param.excessEnergy.thresholdDayTemp | |
EXCESS_ENERGY_COOLING_LIMIT_DAY | float | yes | sParam.heatCircuit[%s].param.excessEnergy.thresholdDayCoolTemp | |
TARGET_TEMPERATURE_NIGHT | float | yes | sParam.heatCircuit[%s].param.reducedSetTemp | |
TARGET_COOLING_TEMPERATURE_NIGHT | float | yes | sParam.heatCircuit[%s].param.reducedCoolSetTemp | |
HEATING_LIMIT_NIGHT | float | yes | sParam.heatCircuit[%s].param.thresholdNightTemp.value | |
COOLING_LIMIT_NIGHT | float | yes | sParam.heatCircuit[%s].param.thresholdNightCoolTemp.value | |
EXCESS_ENERGY_HEATING_LIMIT_NIGHT | float | yes | sParam.heatCircuit[%s].param.excessEnergy.thresholdNightTemp | |
EXCESS_ENERGY_COOLING_LIMIT_NIGHT | float | yes | sParam.heatCircuit[%s].param.excessEnergy.thresholdNightCoolTemp | |
TARGET_TEMPERATURE_AWAY | float | yes | sParam.heatCircuit[%s].param.holidaySetTemp | |
TARGET_TEMPERATURE_OFFSET | float | yes | sParam.heatCircuit[%s].param.offsetRoomTemp | |
OPERATING_MODE | int | yes | HeatCircuitOperatingMode | sParam.heatCircuit[%s].param.operatingMode |
HEAT_REQUEST | int | no | HeatCircuitHeatRequest | sParam.heatCircuit[%s].values.heatRequest |
COOL_REQUEST | int | no | HeatCircuitCoolRequest | sParam.heatCircuit[%s].values.coolRequest |
AWAY_START_DATE | int | yes | sParam.heatCircuit[%s].param.holiday.start | |
AWAY_END_DATE | int | yes | sParam.heatCircuit[%s].param.holiday.stop | |
HEATING_CURVE_OFFSET | float | yes | sParam.heatCircuit[%s].param.heatCurveOffset | |
COOLING_CURVE_OFFSET | float | yes | sParam.heatCircuit[%s].param.coolCurveOffset | |
HEATING_CURVE_SLOPE | float | yes | sParam.heatCircuit[%s].param.heatCurveGradient | |
COOLING_CURVE_SLOPE | float | yes | sParam.heatCircuit[%s].param.coolCurveGradient | |
USE_HEATING_CURVE | str | yes | BoolEnum | sParam.heatCircuit[%s].param.enableHeatCurveLinTab |
HEATING_CURVE | str | yes | sParam.heatCircuit[%s].param.linTab.fileName | |
COOLING_CURVE | str | yes | sParam.heatCircuit[%s].param.coollinTab.fileName | |
HAS_PUMP | str | no | BoolEnum | sParam.options.heatCircuit[%s].hasPump |
HAS_VAR_SPEED_PUMP | str | no | BoolEnum | sParam.options.heatCircuit[%s].hasVarSpeedPump |
PUMP_SPEED | float | no | sParam.heatCircuit[%s].pumpAO.values.setValueScaled |
LineTablePool
Pool of heating curve points.
This is not a real section. Read and write only with client.heat_circuit.get_heating_curve_points()
and client.heat_circuit.set_heating_curve_points().
| Member | Type | Writable | Values | Path |
|---|---|---|---|---|
HEATING_CURVE_NAME | str | no | sParam.linTabPool[%s].name | |
HEATING_CURVE_POINTS | int | yes | sParam.linTabPool[%s].noOfPoints | |
HEATING_CURVE_POINT_X | float | yes | sParam.linTabPool[%s].points[%s].x | |
HEATING_CURVE_POINT_Y | float | yes | sParam.linTabPool[%s].points[%s].y | |
SAVE_HEATING_CURVE | str | yes | sParam.linTabPool[%s].verCnt |
SolarCircuit
The solar circuit endpoint settings.
| Member | Type | Writable | Values | Path |
|---|---|---|---|---|
NAME | str | yes | sParam.solarCircuit[%s].param.name | |
OPERATING_MODE | int | yes | BoolEnum | sParam.solarCircuit[%s].param.operatingMode |
SOURCE_TEMPERATURE | float | no | sParam.solarCircuit[%s].collectorTemp.values.actValue | |
PUMP_1 | float | no | sParam.solarCircuit[%s].values.pump1 | |
PUMP_2 | float | no | sParam.solarCircuit[%s].values.pump2 | |
CURRENT_TEMPERATURE | float | no | sParam.genericHeat[%s].referenceTemp.values.actValue | |
TARGET_TEMPERATURE | float | yes | sParam.genericHeat[%s].param.setTempMax.value | |
HEAT_REQUEST | str | no | BoolEnum | sParam.genericHeat[%s].values.heatRequest |
HEATING_ENERGY | float | no | sParam.solarCircuit[%s].heatMeter.values.accumulatedHeat | |
DAILY_ENERGY | float | no | sParam.solarCircuit[%s].heatMeter.values.heatDay | |
ACTUAL_POWER | float | no | sParam.solarCircuit[%s].heatMeter.values.power | |
PRIORITY_1_BEFORE_2 | str | yes | BoolEnum | sParam.hmiRetainData.consumer1PrioritySolar[%s] |
ExternalHeatSource
External heat source API endpoints.
| Member | Type | Writable | Values | Path |
|---|---|---|---|---|
OPERATING_MODE | int | yes | BoolEnum | sParam.extHeatSource[%s].param.operatingMode |
TARGET_TEMPERATURE | float | no | sParam.extHeatSource[%s].values.setTemp | |
HEAT_REQUEST | str | no | BoolEnum | sParam.extHeatSource[%s].DO.values.setValueB |
OPERATING_TIME | int | no | sParam.extHeatSource[%s].DO.operationalData.operationalTimeS | |
MAX_RUNTIME | int | no | sParam.extHeatSource[%s].DO.operationalData.maxRunTimeS | |
ACTIVATION_COUNTER | int | no | sParam.extHeatSource[%s].DO.operationalData.activationCounter | |
CONSUMING_EXCESS_ENERGY | str | no | BoolEnum | sParam.extHeatSource[%s].values.consumingExcessEnergy |
EXCESS_ENERGY_OPERATING_TIME | int | no | sParam.extHeatSource[%s].operationalDataExcessEnergy.operationalTimeS | |
EXCESS_ENERGY_MAX_RUNTIME | int | no | sParam.extHeatSource[%s].operationalDataExcessEnergy.maxRunTimeS | |
EXCESS_ENERGY_ACTIVATION_COUNTER | int | no | sParam.extHeatSource[%s].operationalDataExcessEnergy.activationCounter | |
USE_EXCESS_ENERGY | str | yes | BoolEnum | sParam.extHeatSource[%s].param.supportExcessEnergy |
MIN_RUNTIME_EXCESS_ENERGY | int | yes | sParam.extHeatSource[%s].param.minRunTimeExcessEnergy |
SwitchValve
Switch valve API endpoints.
| Member | Type | Writable | Values | Path |
|---|---|---|---|---|
POSITION | int | no | SwitchValvePosition | sParam.switchvalve[%s].values.actPosition |
PassiveCooling
Passive cooling API endpoints.
| Member | Type | Writable | Values | Path |
|---|---|---|---|---|
TEMPERATURE | float | no | sParam.passivecooling[%s].TempCoolPassive.values.actValue | |
SWITCH_VALVE_POSITION | int | no | SwitchValvePosition | sParam.passivecooling[%s].SwitchValvePassiveCool.values.actPosition |
CIRCULATION_PUMP_SPEED | float | no | sParam.passivecooling[%s].Pump.values.setValueScaled | |
MIXER_TARGET_TEMPERATURE | float | no | sParam.passivecooling[%s].Mixer.values.setValue | |
MIXER_FLOW_TEMPERATURE | float | no | sParam.passivecooling[%s].Mixer.flowTemp.values.actValue | |
MIXER_POSITION | float | no | MixerSwitchValvePosition | sParam.passivecooling[%s].Mixer.mixer.values.setValueScaled |
Photovoltaics
Photovoltaics API endpoints.
| Member | Type | Writable | Values | Path |
|---|---|---|---|---|
EXCESS_ENERGY_ACTIVE | str | no | BoolEnum | sParam.photovoltaics.values.excessEnergyActive |
EXCESS_POWER | float | no | sParam.photovoltaics.ElectricEnergyMeter.values.power | |
DAILY_ENERGY | float | no | sParam.photovoltaics.ElectricEnergyMeter.values.heatDay | |
TOTAL_ENERGY | float | no | sParam.photovoltaics.ElectricEnergyMeter.values.accumulatedHeat |
Values
Enums of the readable names, returned with human_readable=True and accepted by the setters.
BoolEnum
Boolean values (OFF / ON).
| Member | Value |
|---|---|
OFF | 0 |
ON | 1 |
SystemOperatingMode
Available system operating modes.
| Member | Value |
|---|---|
SETUP | -1 |
STANDBY | 0 |
SUMMER | 1 |
AUTO_HEAT | 2 |
AUTO_COOL | 3 |
AUTO | 4 |
BufferTankOperatingMode
Available buffer tank operating modes.
| Member | Value |
|---|---|
OFF | 0 |
ON | 1 |
HEAT_UP | 2 |
BufferTankExcessEnergyMode
Available buffer tank excess energy modes.
| Member | Value |
|---|---|
OFF | 0 |
HEATING | 1 |
COOLING | 2 |
HotWaterTankOperatingMode
Available hot water tank operating modes.
| Member | Value |
|---|---|
OFF | 0 |
AUTO | 1 |
ON | 2 |
HEAT_UP | 3 |
HotWaterTankExcessEnergyMode
Available hot water tank excess energy modes.
| Member | Value |
|---|---|
OFF | 0 |
HEATING | 1 |
COOLING | 2 |
HeatPumpState
Available heat pump states.
| Member | Value |
|---|---|
STANDBY | 0 |
FLOW | 1 |
AUTO_HEAT | 2 |
DEFROST | 3 |
AUTO_COOL | 4 |
INFLOW | 5 |
PUMP_DOWN | 6 |
SHUTDOWN | 7 |
ERROR | 8 |
HeatPumpSubState
Available heat pump substates. Some substates have more than one value.
| Member | Value |
|---|---|
NONE | 0 |
OIL_PREHEATING | 1 |
PUMP_PRE_RUN | (2, 3) |
RANDOM_DELAY | 4 |
PRESSURE_EQUALIZATION | (5, 21, 22) |
DEFROST_PRE_FLOW | 6 |
DEFROST_MONITORING | 7 |
SNOW_DETECTION | 8 |
FLUSHING | 9 |
DEFROST_INITIALIZATION | 10 |
PREHEAT_FLOW | 11 |
DEFROST | 12 |
DRIP | (13, 25) |
DEFROST_END | 14 |
OPEN | (15, 16) |
COMPRESSOR_POST_RUN | 17 |
PUMP_POST_RUN | 18 |
LUBRICATION_PULSE | 19 |
REDUCED_SPEED | (20, 26) |
COMPRESSOR_DELAY | 23 |
DEFROST_VENTING | 24 |
SWITCH_HEATING_COOLING | 27 |
WAIT_FOR_COMPRESSOR | (28, 33) |
COMPRESSOR_STOP | 29 |
BIVALENT_LOCK | 30 |
LOCKED | 31 |
RETURN_FLOW_OFF | 32 |
MIXER_OPEN | 34 |
ZONE_VALVE | 35 |
ELECTRIC_DEFROST | 36 |
COUNTERFLOW_VALVE | 37 |
HeatPumpOperatingMode
Available heat pump operating modes.
| Member | Value |
|---|---|
OFF | 0 |
ON | 1 |
BACKUP | 2 |
HeatCircuitMode
Available heat circuit modes.
| Member | Value |
|---|---|
HEATING | 0 |
COOLING | 1 |
HEATING_AND_COOLING | 2 |
HEATING_AND_ACTIVE_COOLING | 3 |
HeatCircuitExcessEnergyMode
Available heat circuit excess energy modes.
| Member | Value |
|---|---|
OFF | 0 |
HEATING | 1 |
COOLING | 2 |
HeatCircuitOperatingMode
Available heat circuit operating modes.
| Member | Value |
|---|---|
OFF | 0 |
AUTO | 1 |
DAY | 2 |
NIGHT | 3 |
HOLIDAY | 4 |
PARTY | 5 |
EXTERNAL | 8 |
ROOM_CONTROL | 9 |
SolarCircuitPriority
Available solar circuit consumer priorities.
| Member | Value |
|---|---|
LOW | 14 |
HIGH | 15 |
HeatCircuitHeatRequest
Available heat circuit heat request states.
| Member | Value |
|---|---|
OFF | 0 |
ON | 1 |
FLOW_OFF | 2 |
TEMPORARY_OFF | 3 |
ROOM_OFF | 4 |
OUTDOOR_OFF | 5 |
INFLOW_OFF | 6 |
HeatCircuitCoolRequest
Available heat circuit cool request states.
| Member | Value |
|---|---|
OFF | 0 |
ON | 1 |
FLOW_OFF | 2 |
TEMPORARY_OFF | 3 |
ROOM_OFF | 4 |
OUTDOOR_OFF | 5 |
INFLOW_OFF | 6 |
SwitchValvePosition
Available switch valve positions.
| Member | Value |
|---|---|
NEUTRAL | 0 |
OPEN | 1 |
CLOSED | 2 |
MixerSwitchValvePosition
Available mixer positions.
| Member | Value |
|---|---|
CLOSED | -1 |
OFF | 0 |
OPEN | 1 |
Other constants
| Name | Value |
|---|---|
API_DEFAULT_TIMEOUT | 10 |
MIN_HEATING_CURVE_POINTS | 7 |
MAX_HEATING_CURVE_POINTS | 16 |
PAYLOAD_PREFIX | 'APPL.CtrlAppl' |
ACT_VALUE_SUFFIX | '.values.actValue' |
MESSAGE_ID_SUFFIX | '.state.msgId' |
EndpointPath
The endpoint paths.
| Member | Value |
|---|---|
READ_WRITE_VARS | '/var/readWriteVars' |
READ_VAR_CHILDREN | '/var/readVarChildren' |
DEVICE_CONTROL | '/deviceControl' |
SW_UPDATE | '/swupdate' |
DATE_TIME | '/dateTime' |
SectionPrefix
Prefixes of the grouped read_data response.
| Member | Value |
|---|---|
SYSTEM | 'system' |
BUFFER_TANK | 'buffer_tank' |
HOT_WATER_TANK | 'hot_water_tank' |
HEAT_PUMP | 'heat_pump' |
HEAT_CIRCUIT | 'heat_circuit' |
SOLAR_CIRCUIT | 'solar_circuit' |
EXTERNAL_HEAT_SOURCE | 'external_heat_source' |
SWITCH_VALVE | 'switch_valve' |
PASSIVE_COOLING | 'passive_cooling' |
PHOTOVOLTAICS | 'photovoltaics' |